Technical Parameters
| Model | IFD2020 Dual IR-UV Flame Detector |
| Sensor | UV flame sensor, infrared flame sensor |
| Response spectral range | 185nm~260nm, 4.3μm, 5.0μm |
| Sampling mode | Real-time optical path sampling |
| Display mode | LED indication |
| Status indication | The blinking green lamp indicates the normal operation, and the permanently-illuminated red lamp indicates a fire alarm. |
| Response time | Level I:6-8 seconds |
| Level II:18-22 seconds | |
| Level III:22-26 seconds | |
| Level IV:3-4 seconds | |
| Output signal | 4-20mA current; |
| Faulty relay passive output (AC:3A 250V, DC:3A 30V) | |
| Fire alarm relay passive output (AC:3A 250V, DC:3A 30V) | |
| Operating voltage | DC18-30V |
| Operating current | ≤30mA(DC24V) |
| Installation mode | Wall-mounted or suspended |
| Maximum detection distance | 50m 0.3mx0.3m n-heptane flame |
| Operating temperature | -40~+70°C |
| Operating humidity | ≤95%RH(without condensation) |
| Detection angle | IR: 90° UV: 120° |
| Shell | Aluminum alloy |
| Weight | 0.6Kg±0.05Kg |
| Electric interface | M20X1.5 |
| Explosion-proof mark | Ex db IIC T6 Gb/Ex tb IIIC T80°C Db |
| Degree of protection | IP66 |
Description
The IFD20 dual IR-UV flame detector is a kind of new-type intelligent fire detection equipment. This detector is manufactured with the high-performance dual infrared sensing technology and the ultraviolet detection technology, as well as the infrared sensor equipment with different wavelengths and narrow-band filtering and the ultraviolet flame sensing equipment of the solar blind band. Among these three sensors, the infrared sensor and the UV sensor are used to reflect the central wavelength of the flame information in different bands, and the other infrared sensor is used to monitor other infrared radiation in the environment. Combined with the flicker characteristics of the flame, the radiation spectrum with flame characteristics can be identified as a fire alarm by means of the operational analysis with the high-speed microprocessor and technical algorithm. The UV flame sensing equipment is able to suppress the interference from the sunlight in a good manner, so as to achieve a fast response to and accurate identification of the flame signal. In addition, this detector can be used for either dual infrared detection or single ultraviolet detection, and can be also used for both infrared and ultraviolet detection at the same time.
Product Characteristics
• High measurement accuracy, stable performance, long service life
• 4~20mA standard analog signal output
• Fault and alarm relay node output
• LED display, sensitivity indication, and alarm indication
• Simple mounting bracket, with easy installation
• Low rate of false alarm, for it is based on the actual flame combustion model
• Be provided with special optical lens to realize the reliable optical path transmission
• The magnetic rod is used to adjust the sensitivity, without requiring the removal of the cap.