IFD2020  Flame Detector

IFD2020

IFD2020 Flame Detector

•Sensor: Infrared flame sensor  

•Response spectral range: 4.3μm, 5.0μm  

•Sampling mode: Real-time optical path sampling  

•Display mode: LED indication  

•Operating current: ≤30mA(DC24V)

    Technical Parameters

    Model IFD2020 Triple Infrared Flame Detector 
    Sensor Infrared flame sensor
    Response spectral range 4.3μm, 5.0μm
    Sampling mode Real-time optical path sampling
    Display mode LED indication
    Status indication The blinking green lamp indicates the normal operation, and the permanently-illuminated red lamp indicates a fire alarm.
    Response time Level I:6-8 seconds
    Level II:18-22 seconds
    Level III:22-26 seconds
    Level IV:3-4 seconds
    Output signal 4-20mA current;
    Faulty relay passive output (AC:3A 250V, DC:3A 30V)
    Fire alarm relay passive output (AC:3A 250V, DC:3A 30V)
    Operating voltage DC18-30V
    Operating current ≤30mA(DC24V)
    Installation mode Wall-mounted or suspended
    Maximum detection distance 50m 0.3mx0.3m n-heptane flame
    Operating temperature -40~+70°C
    Operating humidity ≤95%RH(without condensation)
    Detection angle 90°
    Shell Aluminum alloy
    Weight 0.6Kg±0.05Kg
    Electric interface M20X1.5
    Explosion-proof mark Ex db IIC T6 Gb/Ex tb IIIC T80°C Db
    Degree of protection IP66

    Description

    The IFD20 tripe infrared flame detector is a kind of new-type intelligent fire detection equipment. This detector adopts the multi-infrared sensing technology (MIR), and is provided with three infrared sensors with different wavelengths and narrow-band filtering. One sensor is used to reflect the central wavelength of the flame information, and the other two are used to monitor other infrared radiation in the environment. Combined with the flicker characteristics of the flame, the radiation spectrum with flame characteristics can be identified as a fire alarm by means of the operational analysis with the high-speed microprocessor and technical algorithm. This detector can suppress the interferences such as sunlight, lightning, electric welding, thermal radiation, electromagnetic interference, mechanical vibration, etc., is provided with strong anti-interference capacity, and can quickly respond to and accurately identify the flame signal.

    Product Characteristics

    • High measurement accuracy, stable performance, long service life

    • 4~20mA standard analog signal output

    • Fault and alarm relay node output

    • LED display, sensitivity indication, and alarm indication

    • Simple mounting bracket, with easy installation

    • Low rate of false alarm, for it is based on the actual flame combustion model

    • Be provided with special optical lens to realize the reliable optical path transmission

    • The magnetic rod is used to adjust the sensitivity, without requiring the removal of the cap.

    description2